Ozone-depleting Substances and Halocarbon Alternatives Regulations (SOR/2016-137)
Full Document:
- HTMLFull Document: Ozone-depleting Substances and Halocarbon Alternatives Regulations (Accessibility Buttons available) |
- XMLFull Document: Ozone-depleting Substances and Halocarbon Alternatives Regulations [225 KB] |
- PDFFull Document: Ozone-depleting Substances and Halocarbon Alternatives Regulations [507 KB]
Regulations are current to 2024-11-26 and last amended on 2020-08-23. Previous Versions
SCHEDULE 1.1(Subsections 64.4(1) and (2) and 65.02(1))
Products Containing or Designed to Contain an HFC Used as a Refrigerant
Column 1 | Column 2 | Column 3 | Column 4 | |
---|---|---|---|---|
Item | Product | Use | Date | Global Warming Potential (GWP) Limit of Refrigerant Used in Product |
1 | Stand-alone medium-temperature refrigeration system: self-contained refrigeration system with components that are integrated within its structure and that is designed to maintain an internal temperature ≥ 0°C |
| January 1, 2020 | 1 400 |
| January 1, 2025 | 150 | ||
2 | Stand-alone low-temperature refrigeration system: self-contained refrigeration system with components that are integrated within its structure and that is designed to maintain an internal temperature < 0°C but not < -50°C |
| January 1, 2020 | 1 500 |
| January 1, 2025 | 150 | ||
3 | Centralized refrigeration system: refrigeration system with a cooling evaporator in the refrigerated space connected to a compressor rack located in a machinery room and to a condenser located outdoors, and that is designed to maintain an internal temperature at ≥ -50°C | Commercial or industrial | January 1, 2020 | 2 200 |
4 | condensing unit: refrigeration system with at a cooling evaporator in the refrigerated space connected to a compressor and condenser unit that are located in a different location, and that is designed to maintain an internal temperature at ≥ -50°C | Commercial or industrial | January 1, 2020 | 2 200 |
5 | chiller: refrigeration or air-conditioning system that has a compressor, an evaporator and a secondary coolant, other than an absorption chiller | Commercial or industrial | January 1, 2025 | 750 |
6 | mobile refrigeration system: refrigeration system that is normally attached to or installed in, or operates in or with a means of transportation | Commercial or industrial | January 1, 2025 | 2 200 |
- SOR/2017-216, s. 16, err., Vol. 152, No. 11